 3 Phase + Neutral Versions |
Technical data
Standard: IEC61008, GB16916
Rated Voltage (Un):
4pole: AC 400 (415) V
Rated current (In): 25, 40, 63A
Rated residual operating current (IRn): 10, 30, 100, 300, 500mA
Rated residual non-operation current (IRn): 0.5 IRn ~ IRn
Residual current off-time: < 0.3 sec
Type: AC
Ultimate short-circuit breaking capacity (Inc): 6000A
Endurance:
On load: 2000 cycles
Off load: 2000 cycles
Operating Condition
Ambient temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
Altitude above sea level less than 2000 m.
Relative humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
Installation class II or III.
Pollution class II.
Installation method DIN Rail mounting type.
The external magnetism shall not be more than 5 times of terrestrial one.
Product shall be installed vertically at the place where there shall be no severe impact and vibration.
The product is switched on when the handle is at upper position.
|