 MCB/RCCB Combinations |
MCB/RCCB (or RCBO in short) protects the allocated power circuit against overload, short-circuit and earth-leakage.
Application
Protection against the effects of earth leakage overload and short circuit currents.
2P switching of Phase and Neutral. The Phase is only protected against overload and short circuit.
To be applied in commercial, industrial and domestic electrical distribution systems.
Note: must mot be used as the sole means of providing protection against direct contact.
The RCBO incorporates a residual current operated electromagnetic release which operates without any auxiliary source of supply to open a circuit automatically in the case of an earth leakage fault between phase and earth greater than or equal to In.
The RCBO combined MCB&RCCB provides:
Protection against indirect contact
Complementary protection against direct contact
Protection for the installation against in sulation faults
Technical data
Standard: IEC61009 GB16917
Rated Voltage (Un):AC 230(240)V
Rated Current (In): 1, 2, 3, 4, 6, 10, 16, 20, 32, 40A
Number of pole: 1P+N
Rated residual operating current ( IRn): 30, 100, 300, 500mA
Type: AC
Ultimate short-circuit breaking capacity (Inc):6000A
Endurance:
On load: 2000 cycles
Off load: 2000 cycles
Operating Condition
Circumstance temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
Altitude above sea level less than 2000 M.
Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
Installation class II or III.
Pollution class II.
Installation method DIN Rail mounting type.
|