 Modular Isolators |
Isolators may be used to savely disconnect circuits from the mains.
Application
For use as switch disconnectors in all types of circuit as defined in the 16th Edition of the IEE Wiring regulations.
Technical data
Standards: IEC60947-3, GB14048.3
Current rating: 63, 80, 100, 160, 250A
Voltage rating: AC 230(240) / 400(415)V
Poles:1P, 2P, 3P, 4P
Ultimate short-circuit breaking capacity (Inc): 10000A
Cable capacity: tunnel terminal for cable up to 50mm2
Endurance:
63A: 20000 cycles
80?100A: 10000 cycles
Operating Condition
Ambient temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
Altitude above sea level less than 2000 m.
Relative humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
Installation class II or III.
Pollution class II.
Installation method DIN Rail mounting type.
Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.
|